Battery Bank Amp Hour Calculator
Convert between amp-hours, kilowatt-hours and runtime for a battery bank.
About Battery Bank Amp Hour Calculator
Amp-hours only describe energy once multiplied by voltage. The C-rate matters because high discharge rates reduce effective capacity, especially in lead-acid chemistries. A battery rated at the 20-hour rate delivers noticeably less capacity when discharged in two hours, an effect described by Peukert’s law.
Formula
Battery Bank Amp Hour
kWh = Ah × V ÷ 1,000; runtime = usable kWh × 1,000 ÷ load watts
- C-rate
- Discharge current as a multiple of capacity, affecting available capacity
Worked example
With the default values below, Battery Bank Amp Hour Calculator returns Bank Energy of 19.2000. Change any input above and every figure here is recalculated in your browser.
Inputs used
- Bank capacityminimum 0 Ah
- 400 Ah
- System voltageminimum 1 V
- 48 V
- Loadminimum 1 W
- 1,000 W
- Usable depth of dischargeaccepts 0–100 %
- 80 %
Results
- Bank Energy
- 19.2000 kWh
- Usable Energy
- 15.3600 kWh
- Runtime at That Load
- 15.360 h
- Load Current
- 20.833 A
- Discharge C-Rate
- 0.0521 C
Step by step
- 1Values used
- 2Battery Bank Amp Hour
- 3Bank Energy= 19.2000 kWh
- 4Usable Energy= 15.3600 kWh
- 5Runtime at That Load= 15.360 h
- 6Load Current= 20.833 A
- 7Discharge C-Rate= 0.0521 C
Assumptions and limits
- The result is derived only from the 4 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax or compounding frequency into account.
- Figures are rounded for display to 4 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Frequently Asked Questions
How is Battery Bank Amp Hour calculated?
kWh = Ah × V ÷ 1,000; runtime = usable kWh × 1,000 ÷ load watts Amp-hours only describe energy once multiplied by voltage. The C-rate matters because high discharge rates reduce effective capacity, especially in lead-acid chemistries.
Why does Battery Bank Amp Hour matter?
A battery rated at the 20-hour rate delivers noticeably less capacity when discharged in two hours, an effect described by Peukert’s law.
What values do I need to enter?
This calculator takes 4 inputs: Bank capacity, System voltage, Load, Usable depth of discharge. The pre-filled defaults are a realistic starting point — replace them with figures from your own environment for a result you can act on.
Related Calculators
You might also need
- Solar Panel Output CalculatorCommonly used together
- Solar Panel Size CalculatorCommonly used together
- Solar System Size CalculatorCommonly used together
- Air Conditioner Running CostAlso in Solar, Energy & Sustainability
- Annual Electricity CostAlso in Solar, Energy & Sustainability
- Battery Bank Size CalculatorAlso in Solar, Energy & Sustainability