The Siegert formula estimates the heat lost up the stack from net flue temperature and residual oxygen: loss = ΔT x (A2 / (21 - O2) + B), with fuel-specific constants. Efficiency is 100 percent minus that loss, so cutting either excess air or stack temperature improves it directly.

Formulas

Siegert stack loss

Loss % = (Tstack - Tair) x (A2 / (21 - O2) + B)

A2
0.66 gas, 0.68 oil, 0.65 coal
B
0.009 gas, 0.007 oil, 0.005 coal

Efficiency

η = 100 - stack loss %

Worked example

With the default values below, Combustion Efficiency Calculator returns Combustion efficiency of 82.51%. Change any input above and every figure here is recalculated in your browser.

Inputs used

Stack temperatureminimum 50 °F
400 °F
Combustion air temperatureminimum -40 °F
70 °F
Flue oxygenaccepts 0.1–20 %
6 %
Fuelone of Natural gas, Light fuel oil, Coal
Natural gas

Results

Combustion efficiency
82.51% %
Dry flue gas loss
17.49% %
Excess air
40.3% %
Net stack temperature
330.0 °F

Step by step

  1. 1Values used
  2. 2Siegert stack loss
  3. 3Efficiency
  4. 4Combustion efficiency= 82.51 %
  5. 5Dry flue gas loss= 17.49 %
  6. 6Excess air= 40.3 %
  7. 7Net stack temperature= 330.0 °F

Assumptions and limits

  • The result is derived only from the 4 inputs listed above. Anything not among them is not part of the calculation.
  • In particular, this calculator does not take inflation, tax, fees or charges or compounding frequency into account.
  • Figures are rounded for display to 2 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.

How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.

Frequently Asked Questions

How is the Combustion Efficiency figure worked out?

Loss % = (Tstack - Tair) x (A2 / (21 - O2) + B). The Siegert formula estimates the heat lost up the stack from net flue temperature and residual oxygen: loss = ΔT x (A2 / (21 - O2) + B), with fuel-specific constants.

Why can a condensing boiler beat this number?

Siegert accounts only for dry flue gas loss on a net calorific basis. A condensing appliance also recovers latent heat from the water vapour, which this method does not credit.

What values do I need to enter?

This calculator takes 4 inputs: Stack temperature, Combustion air temperature, Flue oxygen, Fuel. The pre-filled defaults are a realistic worked example — replace them with your own site or project figures.

Combustion Efficiency Calculator | Calcrivo