Compressor Capacity Calculator
Work out compressor capacity instantly with clear inputs, formula shown and shareable results.
About Compressor Capacity Calculator
Compressor capacity is mass flow multiplied by the net refrigerating effect, the enthalpy the refrigerant gains crossing the evaporator. Because a ton of refrigeration is 12,000 BTU/h, dividing gives nominal tonnage, and mass flow per ton is a quick sanity check against published compressor data.
Formulas
Capacity
Q = mass flow x (h1 - h4)
- h1
- Enthalpy leaving evaporator
- h4
- Enthalpy entering evaporator
Tonnage
tons = Q / 12000
Worked example
With the default values below, Compressor Capacity Calculator returns Refrigeration capacity of 20,400. Change any input above and every figure here is recalculated in your browser.
Inputs used
- Refrigerant mass flowminimum 1 lb/h
- 300 lb/h
- Enthalpy leaving evaporatorminimum 1 BTU/lb
- 108 BTU/lb
- Enthalpy entering evaporatorminimum 0 BTU/lb
- 40 BTU/lb
Results
- Refrigeration capacity
- 20,400 BTU/h
- Capacity in tons
- 1.70 tons
- Net refrigerating effect
- 68.0 BTU/lb
- Mass flow per ton
- 176.47 lb/h/ton
Step by step
- 1Values used
- 2Capacity
- 3Tonnage
- 4Refrigeration capacity= 20,400 BTU/h
- 5Capacity in tons= 1.70 tons
- 6Net refrigerating effect= 68.0 BTU/lb
- 7Mass flow per ton= 176.47 lb/h/ton
Assumptions and limits
- The result is derived only from the 3 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax, fees or charges or compounding frequency into account.
- Figures are rounded for display to 2 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Frequently Asked Questions
How is the Compressor Capacity figure worked out?
Q = mass flow x (h1 - h4). Compressor capacity is mass flow multiplied by the net refrigerating effect, the enthalpy the refrigerant gains crossing the evaporator.
Why does capacity fall in hot weather?
A higher condensing temperature raises the enthalpy of the liquid entering the evaporator, shrinking the net refrigerating effect while also cutting volumetric efficiency.
What values do I need to enter?
This calculator takes 3 inputs: Refrigerant mass flow, Enthalpy leaving evaporator, Enthalpy entering evaporator. The pre-filled defaults are a realistic worked example — replace them with your own site or project figures.
Related Calculators
You might also need
- Humidifier Capacity CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Air Compressor Sizing CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Cooling Tower Capacity CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Bearing Life CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Belt Length CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Belt Tension CalculatorAlso in HVAC, Plumbing & Mechanical Trades