Data Centre Cooling Load Calculator
Work out data centre cooling load instantly with clear inputs, formula shown and shareable results.
About Data Centre Cooling Load Calculator
Essentially all electrical energy entering IT equipment leaves as heat, so cooling capacity must match the full IT load plus lighting and losses, with margin. The coefficient of performance is how much heat is moved per unit of electricity consumed, so a COP of 3.5 means cooling adds roughly 29 percent to the facility's electrical draw.
Formula
Cooling load
heat = IT load + other loads; capacity = heat x (1 + margin); cooling electrical draw = capacity / COP; 1 ton = 3.517 kW
Worked example
With the default values below, Data Centre Cooling Load Calculator returns Cooling capacity required of 225.6. Change any input above and every figure here is recalculated in your browser.
Inputs used
- IT equipment loadminimum 0.1 kW
- 180 kW
- Lighting and other loadsminimum 0 kW
- 8 kW
- Cooling coefficient of performanceaccepts 0.5–10
- 3.5
- Design marginaccepts 0–100 %
- 20 %
Results
- Cooling capacity required
- 225.6 kW
- Electrical power the cooling consumes
- 64.5 kW
- Cooling capacity in tons
- 64.1 tons
- Total facility electrical load
- 252.5 kW
Step by step
- 1Values used
- 2Cooling load
- 3Cooling capacity required= 225.6 kW
- 4Electrical power the cooling consumes= 64.5 kW
- 5Cooling capacity in tons= 64.1 tons
- 6Total facility electrical load= 252.5 kW
Assumptions and limits
- The result is derived only from the 4 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax or compounding frequency into account.
- Figures are rounded for display to 1 decimal place, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Frequently Asked Questions
Why does IT load equal heat load?
Because computers do no mechanical work. Every watt consumed is converted to heat, which is why the two figures are treated as identical in facility design.
What improves COP?
Higher supply air temperatures, hot and cold aisle containment, free cooling using outside air, and liquid cooling for high-density racks.
Related Calculators
- Load Average Interpretation Calculator
- Account Lockout Policy Calculator
- Backup Size With Retention Calculator
- Bare Metal Sizing Calculator
- Bash Script Runtime Calculator
- Block Size Overhead Calculator
- Compression Ratio Savings Calculator
- Container vs VM Overhead Calculator
- Context Switch Rate Calculator
- CPU Steal Time Impact Calculator
You might also need
- Load Average Interpretation CalculatorAlso in Linux & System Administration
- Container vs VM Overhead CalculatorAlso in Linux & System Administration
- CPU Utilisation CalculatorAlso in Linux & System Administration
- Free Memory Estimate CalculatorAlso in Linux & System Administration
- Group Quota CalculatorAlso in Linux & System Administration
- Journal Size CalculatorAlso in Linux & System Administration