Drain Pipe Sizing Calculator
Work out drain pipe sizing instantly with clear inputs, formula shown and shareable results.
About Drain Pipe Sizing Calculator
Gravity drains are sized to run no more than half full so air can move above the water and protect trap seals. Manning's equation, Q = (1.486/n) A R^(2/3) S^(1/2), gives the half-full capacity of each standard size, and the smallest size that carries the fixture unit design flow is selected.
Formulas
Manning capacity
Q = (1.486 / n) x A x R^(2/3) x S^(1/2), evaluated half full
Design flow
GPM ≈ 2.5 x DFU^0.6
Worked example
With the default values below, Drain Pipe Sizing Calculator returns Drain size required of 3.0. Change any input above and every figure here is recalculated in your browser.
Inputs used
- Total drainage fixture unitsminimum 1 DFU
- 24 DFU
- Pipe slopeminimum 0.2 %
- 2.08 %
- Manning roughness nminimum 0.008
- 0.013
Results
- Drain size required
- 3.0 in
- Design flow
- 16.8 GPM
- Capacity of chosen size at half full
- 28.6 GPM
- Capacity used
- 58.8% %
Step by step
- 1Values used
- 2Manning capacity
- 3Design flow
- 4Drain size required= 3.0 in
- 5Design flow= 16.8 GPM
- 6Capacity of chosen size at half full= 28.6 GPM
- 7Capacity used= 58.8 %
Assumptions and limits
- The result is derived only from the 3 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax, fees or charges or compounding frequency into account.
- Figures are rounded for display to 1 decimal place, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
- Preliminary estimate only. Drainage sizing must follow the fixture unit tables and slope requirements of the plumbing code adopted locally.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Preliminary estimate only. Drainage sizing must follow the fixture unit tables and slope requirements of the plumbing code adopted locally.
Frequently Asked Questions
How is the Drain Pipe Sizing figure worked out?
Q = (1.486 / n) x A x R^(2/3) x S^(1/2), evaluated half full. Gravity drains are sized to run no more than half full so air can move above the water and protect trap seals.
Why is a steeper slope not always better?
Above about 4 percent the water outruns the solids, leaving them stranded in the pipe. The classic quarter inch per foot balances velocity against carrying capacity.
What values do I need to enter?
This calculator takes 3 inputs: Total drainage fixture units, Pipe slope, Manning roughness n. The pre-filled defaults are a realistic worked example — replace them with your own site or project figures.
Related Calculators
You might also need
- Condensate Drain Sizing CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Gas Pipe Sizing CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Steam Pipe Sizing CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Vent Pipe Sizing CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Water Supply Pipe Sizing CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Boiler Sizing CalculatorAlso in HVAC, Plumbing & Mechanical Trades