Fresh Air Requirement Calculator
Work out fresh air requirement instantly with clear inputs, formula shown and shareable results.
About Fresh Air Requirement Calculator
Fresh air demand scales with occupancy. Multiplying head count by the per-person rate gives total outdoor airflow, and dividing the sedentary carbon dioxide generation rate of about 0.0106 CFM per person by the ventilation rate per person predicts the steady-state indoor concentration above the outdoor baseline of roughly 420 ppm.
Formulas
Fresh air
CFM = occupants x CFM per person; L/s = CFM x 0.4719
Steady-state CO₂
ppm = outdoor ppm + 10600 / (CFM per person)
Worked example
With the default values below, Fresh Air Requirement Calculator returns Fresh air required of 600. Change any input above and every figure here is recalculated in your browser.
Inputs used
- Occupantsminimum 1
- 40
- Fresh air per personminimum 1 CFM
- 15 CFM
- Room volumeminimum 1 ft³
- 12,000 ft³
Results
- Fresh air required
- 600 CFM
- Equivalent metric flow
- 283.2 L/s
- Fresh air changes per hour
- 3.00 ACH
- Steady-state CO₂ estimate
- 1,127 ppm
Step by step
- 1Values used
- 2Fresh air
- 3Steady-state CO₂
- 4Fresh air required= 600 CFM
- 5Equivalent metric flow= 283.2 L/s
- 6Fresh air changes per hour= 3.00 ACH
- 7Steady-state CO₂ estimate= 1,127 ppm
Assumptions and limits
- The result is derived only from the 3 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax, fees or charges or compounding frequency into account.
- Figures are rounded for display to 2 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Frequently Asked Questions
How is the Fresh Air Requirement figure worked out?
CFM = occupants x CFM per person; L/s = CFM x 0.4719. Fresh air demand scales with occupancy.
Why is 15 CFM per person common?
It is the classic office rate that holds carbon dioxide near 1100 ppm, the level long used as a proxy for acceptable bio-effluent dilution.
What values do I need to enter?
This calculator takes 3 inputs: Occupants, Fresh air per person, Room volume. The pre-filled defaults are a realistic worked example — replace them with your own site or project figures.
Related Calculators
You might also need
- Enthalpy Of Air CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Air Compressor Sizing CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Air Conditioner Sizing CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Compressed Air Consumption CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Mixing Air Streams CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Air Changes Per Hour CalculatorAlso in HVAC, Plumbing & Mechanical Trades