Power Plant Heat Rate Calculator
Work out power plant heat rate instantly with clear inputs, formula shown and shareable results.
About Power Plant Heat Rate Calculator
Heat rate is fuel energy input per unit of electrical output, in kilojoules per kilowatt-hour. It is the reciprocal of efficiency: efficiency = 3600 / heat rate. Net heat rate uses output after station auxiliaries, which consume 5-8% of gross output in a coal plant and 2-3% in a gas turbine plant.
Formulas
Heat rate
Heat rate (kJ/kWh) = fuel energy input / net electrical output
Efficiency
Efficiency % = 3600 x 100 / heat rate
Worked example
With the default values below, Power Plant Heat Rate Calculator returns Net Heat Rate of 9,042.6. Change any input above and every figure here is recalculated in your browser.
Inputs used
- Fuel Energy Inputminimum 0 GJ/hour
- 8,500 GJ/hour
- Net Electrical Outputminimum 0 MW
- 1,000 MW
- Auxiliary Consumptionaccepts 0–40 %
- 6 %
- Fuel Costminimum 0 per GJ
- 8 per GJ
Results
- Net Heat Rate
- 9,042.6
- Thermal Efficiency
- 39.812%
- Net Output After Auxiliaries
- 940.00
- Fuel Cost Per MWh
- $72.340
Step by step
- 1Values used
- 2Heat rate
- 3Efficiency
- 4Net Heat Rate= 9,042.6
- 5Thermal Efficiency= 39.812
- 6Net Output After Auxiliaries= 940.00
- 7Fuel Cost Per MWh= 72.340
Assumptions and limits
- The result is derived only from the 4 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax or compounding frequency into account.
- Figures are rounded for display to 3 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Frequently Asked Questions
What heat rates are typical?
About 9500-11,000 kJ/kWh for a subcritical coal unit (33-38%), 8000-8500 for supercritical, and 6000-6600 for a modern combined cycle gas plant (55-60%).
Why report net rather than gross heat rate?
Only net output reaches the grid and earns revenue. A plant with efficient auxiliaries has a better net heat rate even at the same boiler and turbine performance.
Related Calculators
- Betz Limit Power Calculator
- Drilling Rate Of Penetration Calculator
- Gas Compression Power Calculator
- Geothermal Heat Output Calculator
- Hydro Power Output Calculator
- Mill Power Requirement Calculator
- Mineral Recovery Rate Calculator
- Oil Well Production Rate Calculator
- Plant Load Factor Calculator
- Power Purchase Agreement Value Calculator
You might also need
- Gas Compression Power CalculatorAlso in Energy, Oil, Gas & Mining
- Betz Limit Power CalculatorAlso in Energy, Oil, Gas & Mining
- Drilling Rate Of Penetration CalculatorAlso in Energy, Oil, Gas & Mining
- Geothermal Heat Output CalculatorAlso in Energy, Oil, Gas & Mining
- Hydro Power Output CalculatorAlso in Energy, Oil, Gas & Mining
- Mill Power Requirement CalculatorAlso in Energy, Oil, Gas & Mining