PUE Efficiency Calculator
Work out pue efficiency instantly with clear inputs, formula shown and shareable results.
About PUE Efficiency Calculator
PUE is total facility power divided by IT power, so 1.0 would mean every watt reaches the equipment. Hyperscale operators reach 1.1 with free cooling and containment; a typical enterprise computer room sits between 1.6 and 2.0, meaning as much energy goes on cooling and losses as on computing. Improving PUE is pure operating cost reduction.
Formula
PUE
PUE = total facility power / IT equipment power; overhead = total - IT; saving at target = (current total - IT x target PUE) x hours x price
Worked example
With the default values below, PUE Efficiency Calculator returns Power usage effectiveness of 1.444. Change any input above and every figure here is recalculated in your browser.
Inputs used
- Total facility powerminimum 0.1 kW
- 260 kW
- IT equipment powerminimum 0.1 kW
- 180 kW
- Electricity price per kWhminimum 0
- 0.18
- Target PUEaccepts 1–4
- 1.3
Results
- Power usage effectiveness
- 1.444
- Non-IT facility power
- 80.0 kW
- Annual saving at the target PUE
- $41,025
- Efficiency rating
- Good - modern facility
Step by step
- 1Values used
- 2PUE
- 3Power usage effectiveness= 1.444
- 4Non-IT facility power= 80.0 kW
- 5Annual saving at the target PUE= 41,025
- 6Efficiency rating= Good - modern facility
Assumptions and limits
- The result is derived only from the 4 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax, fees or charges or compounding frequency into account.
- Figures are rounded for display to 3 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Frequently Asked Questions
Can PUE be below 1?
No, not by definition. Facilities that reuse waste heat report a separate metric, ERE, which can fall below 1 because exported heat is credited.
Does a low PUE mean an efficient data centre?
Not necessarily. PUE improves when IT load rises even if that load is doing nothing useful, so it must be read alongside utilisation and work-per-watt measures.
Related Calculators
- Account Lockout Policy Calculator
- Backup Size With Retention Calculator
- Bare Metal Sizing Calculator
- Bash Script Runtime Calculator
- Block Size Overhead Calculator
- Compression Ratio Savings Calculator
- Container vs VM Overhead Calculator
- Context Switch Rate Calculator
- CPU Steal Time Impact Calculator
- CPU Utilisation Calculator
You might also need
- Container vs VM Overhead CalculatorAlso in Linux & System Administration
- CPU Utilisation CalculatorAlso in Linux & System Administration
- Free Memory Estimate CalculatorAlso in Linux & System Administration
- Group Quota CalculatorAlso in Linux & System Administration
- Journal Size CalculatorAlso in Linux & System Administration
- LVM Sizing CalculatorAlso in Linux & System Administration