Reactive Power Calculator
Calculate reactive power and the correction needed to reduce it.
About Reactive Power Calculator
Reactive power circulates without doing work but still occupies supply capacity. Capacitors supply leading reactive power that cancels the lagging reactive power of motors, which is why correction is sized in kVAR. Correcting from 0.75 to 0.95 releases about a fifth of the apparent power, often deferring a transformer upgrade entirely.
Formula
Reactive Power
Q = P tan φ; correction = P (tan φ₁ − tan φ₂)
- tan φ
- Ratio of reactive to real power at a given power factor
Worked example
With the default values below, Reactive Power Calculator returns Present Reactive Power of 44.0959. Change any input above and every figure here is recalculated in your browser.
Inputs used
- Real powerminimum 0 kW
- 50 kW
- Present power factoraccepts 0.01–1
- 0.75
- Target power factoraccepts 0.01–1
- 0.95
Results
- Present Reactive Power
- 44.0959 kVAR
- Reactive Power at the Target
- 16.4342 kVAR
- Correction Capacitance Required
- 27.6616 kVAR
- Present Apparent Power
- 66.6667 kVA
- Apparent Power Released
- 14.0351 kVA
Step by step
- 1Values used
- 2Reactive Power
- 3Present Reactive Power= 44.0959 kVAR
- 4Reactive Power at the Target= 16.4342 kVAR
- 5Correction Capacitance Required= 27.6616 kVAR
- 6Present Apparent Power= 66.6667 kVA
- 7Apparent Power Released= 14.0351 kVA
Assumptions and limits
- The result is derived only from the 3 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax, fees or charges or compounding frequency into account.
- Figures are rounded for display to 4 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Frequently Asked Questions
How is Reactive Power calculated?
Q = P tan φ; correction = P (tan φ₁ − tan φ₂) Reactive power circulates without doing work but still occupies supply capacity. Capacitors supply leading reactive power that cancels the lagging reactive power of motors, which is why correction is sized in kVAR.
Why does Reactive Power matter?
Correcting from 0.75 to 0.95 releases about a fifth of the apparent power, often deferring a transformer upgrade entirely.
What values do I need to enter?
This calculator takes 3 inputs: Real power, Present power factor, Target power factor. The pre-filled defaults are a realistic starting point — replace them with figures from your own environment for a result you can act on.
Related Calculators
You might also need
- AC Power CalculatorCommonly used together
- DC Power CalculatorCommonly used together
- Electrical Power CalculatorCommonly used together
- Power Factor Correction CalculatorAlso in Electronics & Electrical
- Ohms Law CalculatorAlso in Electronics & Electrical
- 555 Timer CalculatorAlso in Electronics & Electrical