Sewer Pipe Sizing Calculator
Work out sewer pipe sizing instantly with clear inputs, formula shown and shareable results.
About Sewer Pipe Sizing Calculator
Gravity sewers are sized with Manning's equation, evaluated at full bore, then limited to a proportional depth of 70-75 percent so air can move above the flow. The smallest standard diameter whose limited capacity exceeds the design peak flow is selected, and full bore velocity is checked against the self-cleansing minimum.
Formulas
Manning capacity
Q full = (1/n) x (D/4)^(2/3) x S^(1/2) x pi D² / 4
Selection
Choose the smallest diameter where Q full x fill ratio is at least the design flow
Worked example
With the default values below, Sewer Pipe Sizing Calculator returns Pipe size required of 225. Change any input above and every figure here is recalculated in your browser.
Inputs used
- Design peak flowminimum 0.01 L/s
- 12 L/s
- Pipe gradientminimum 0.05 %
- 1 %
- Manning roughness nminimum 0.008
- 0.013
- Maximum proportional depthaccepts 0.1–1
- 0.75
Results
- Pipe size required
- 225 mm
- Full bore capacity of that size
- 44.90 L/s
- Full bore velocity
- 1.129 m/s
- Design flow as share of capacity
- 26.7% %
Step by step
- 1Values used
- 2Manning capacity
- 3Selection
- 4Pipe size required= 225 mm
- 5Full bore capacity of that size= 44.90 L/s
- 6Full bore velocity= 1.129 m/s
- 7Design flow as share of capacity= 26.7 %
Assumptions and limits
- The result is derived only from the 4 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax, fees or charges or compounding frequency into account.
- Figures are rounded for display to 3 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
- Preliminary estimate only. Sewer design must follow the drainage code and authority standards, and be verified by a qualified engineer.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Preliminary estimate only. Sewer design must follow the drainage code and authority standards, and be verified by a qualified engineer.
Frequently Asked Questions
How is the Sewer Pipe Sizing figure worked out?
Q full = (1/n) x (D/4)^(2/3) x S^(1/2) x pi D² / 4. Gravity sewers are sized with Manning's equation, evaluated at full bore, then limited to a proportional depth of 70-75 percent so air can move above the flow.
Why not run pipes full?
A sewer running full has no ventilation path, so pressure fluctuations break trap seals upstream and septic conditions and odour develop. It also leaves no capacity for peaks.
What values do I need to enter?
This calculator takes 4 inputs: Design peak flow, Pipe gradient, Manning roughness n, Maximum proportional depth. The pre-filled defaults are a realistic worked example — replace them with your own site or project figures.
Related Calculators
You might also need
- Downpipe Sizing CalculatorAlso in Construction & Civil Engineering
- Lift Sizing CalculatorAlso in Construction & Civil Engineering
- Pipe Weight CalculatorAlso in Construction & Civil Engineering
- Pipe Friction Loss CalculatorAlso in Construction & Civil Engineering
- Septic Tank Sizing CalculatorAlso in Construction & Civil Engineering
- Water Velocity In Pipe CalculatorAlso in Construction & Civil Engineering