Sprinkler System Flow Calculator
Work out sprinkler system flow instantly with clear inputs, formula shown and shareable results.
About Sprinkler System Flow Calculator
Sprinkler system demand is design density multiplied by the assumed area of operation, since one millimetre per minute over one square metre is one litre per minute. Individual sprinkler discharge follows the orifice relation q = K sqrt(p), so dividing total flow by sprinkler discharge shows how many heads the design implies.
Formulas
System flow
L/min = design density mm/min x area of operation m²
Sprinkler discharge
q = K x sqrt(pressure in bar)
Worked example
With the default values below, Sprinkler System Flow Calculator returns Total system flow of 700.0. Change any input above and every figure here is recalculated in your browser.
Inputs used
- Design densityminimum 0.5 mm/min
- 5 mm/min
- Assumed area of operationminimum 1 m²
- 140 m²
- Sprinkler K factorminimum 10
- 80
- Pressure at the sprinklerminimum 0.1 bar
- 1 bar
Results
- Total system flow
- 700.0 L/min
- Total system flow
- 11.667 L/s
- Flow per sprinkler
- 80.00 L/min
- Sprinklers assumed operating
- 9
Step by step
- 1Values used
- 2System flow
- 3Sprinkler discharge
- 4Total system flow= 700.0 L/min
- 5Total system flow= 11.667 L/s
- 6Flow per sprinkler= 80.00 L/min
- 7Sprinklers assumed operating= 9
Assumptions and limits
- The result is derived only from the 4 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax, fees or charges or compounding frequency into account.
- Figures are rounded for display to 3 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
- Preliminary estimate only. Sprinkler system design must be carried out by a qualified fire protection engineer to the applicable standard and hydraulically calculated node by node.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Preliminary estimate only. Sprinkler system design must be carried out by a qualified fire protection engineer to the applicable standard and hydraulically calculated node by node.
Frequently Asked Questions
How is the Sprinkler System Flow figure worked out?
L/min = design density mm/min x area of operation m². Sprinkler system demand is design density multiplied by the assumed area of operation, since one millimetre per minute over one square metre is one litre per minute.
Why an assumed area of operation?
Not every sprinkler in a building operates in a fire. Standards define a design area, typically 72-260 square metres by hazard class, that the water supply must cover simultaneously.
What values do I need to enter?
This calculator takes 4 inputs: Design density, Assumed area of operation, Sprinkler K factor, Pressure at the sprinkler. The pre-filled defaults are a realistic worked example — replace them with your own site or project figures.
Related Calculators
You might also need
- Pipe Diameter For Flow CalculatorAlso in Construction & Civil Engineering
- Aggregate Tonnage CalculatorAlso in Construction & Civil Engineering
- Asphalt Quantity CalculatorAlso in Construction & Civil Engineering
- Asphalt Tonnage CalculatorAlso in Construction & Civil Engineering
- Backfill Quantity CalculatorAlso in Construction & Civil Engineering
- Beam Load CalculatorAlso in Construction & Civil Engineering