Air Change For Contaminant Control Calculator
Work out air change for contaminant control instantly with clear inputs, formula shown and shareable results.
About Air Change For Contaminant Control Calculator
Dilution ventilation airflow is the contaminant generation rate divided by the acceptable concentration, multiplied by a mixing factor because real rooms never mix perfectly. K ranges from about 1.5 for good mixing with the source far from workers, to 10 for poor mixing with the source in the breathing zone.
Formula
Dilution airflow
Q = G x K / C
- G
- Generation rate, mg/min
- C
- Target concentration, mg/m³
- K
- Mixing factor 1.5 to 10
Worked example
With the default values below, Air Change For Contaminant Control Calculator returns Dilution airflow required of 30.00. Change any input above and every figure here is recalculated in your browser.
Inputs used
- Contaminant generation rateminimum 0.01 mg/min
- 50 mg/min
- Target airborne concentrationminimum 0.001 mg/m³
- 5 mg/m³
- Mixing factor Kaccepts 1–10
- 3
- Room volumeminimum 0.1 m³
- 200 m³
Results
- Dilution airflow required
- 30.00 m³/min
- Airflow in cubic feet per minute
- 1,059 CFM
- Air changes per hour required
- 9.00 ACH
- Airflow assuming perfect mixing
- 10.00 m³/min
Step by step
- 1Values used
- 2Dilution airflow
- 3Dilution airflow required= 30.00 m³/min
- 4Airflow in cubic feet per minute= 1,059 CFM
- 5Air changes per hour required= 9.00 ACH
- 6Airflow assuming perfect mixing= 10.00 m³/min
Assumptions and limits
- The result is derived only from the 4 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax, fees or charges or compounding frequency into account.
- Figures are rounded for display to 2 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
- Preliminary estimate only. Ventilation for contaminant control must be designed by a qualified engineer or occupational hygienist to a recognised industrial ventilation standard.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Preliminary estimate only. Ventilation for contaminant control must be designed by a qualified engineer or occupational hygienist to a recognised industrial ventilation standard.
Frequently Asked Questions
How is the Air Change For Contaminant Control figure worked out?
Q = G x K / C. Dilution ventilation airflow is the contaminant generation rate divided by the acceptable concentration, multiplied by a mixing factor because real rooms never mix perfectly.
When is dilution ventilation the wrong choice?
For highly toxic materials, high generation rates, or where the source is close to the worker. In those cases local exhaust at the source is the only reliable control.
What values do I need to enter?
This calculator takes 4 inputs: Contaminant generation rate, Target airborne concentration, Mixing factor K, Room volume. The pre-filled defaults are a realistic worked example — replace them with your own site or project figures.
Related Calculators
- Audit Score For Compliance Calculator
- Lighting Level For Task Calculator
- Smoke Control Airflow Calculator
- Two Hand Control Distance Calculator
- Accident Cost Estimate Calculator
- Anchor Point Load Calculator
- As Low As Reasonably Practicable Cost Calculator
- Assembly Point Area Calculator
- Bow Tie Barrier Count Calculator
- Cartridge Service Life Calculator
You might also need
- Smoke Control Airflow CalculatorAlso in Occupational Safety, Ergonomics & Risk
- Audit Score For Compliance CalculatorAlso in Occupational Safety, Ergonomics & Risk
- Lighting Level For Task CalculatorAlso in Occupational Safety, Ergonomics & Risk
- Two Hand Control Distance CalculatorAlso in Occupational Safety, Ergonomics & Risk
- Exit Capacity CalculatorAlso in Occupational Safety, Ergonomics & Risk
- Glare Index CalculatorAlso in Occupational Safety, Ergonomics & Risk