Contactor Sizing Calculator
Work out contactor sizing instantly with clear inputs, formula shown and shareable results.
About Contactor Sizing Calculator
Contactor selection starts from motor full load current, then applies the utilisation category: AC-3 for normal starting, AC-4 for plugging and jogging where the contacts break locked-rotor current and need roughly double the rating. High starting frequency adds a further factor.
Formula
Contactor sizing
required rating = motor FLC x category factor x starting frequency factor
Worked example
With the default values below, Contactor Sizing Calculator returns Contactor rating required of 17. Change any input above and every figure here is recalculated in your browser.
Inputs used
- Motor rating
- 7.5 kW
- Supply voltage
- 400 V
- Utilisation categoryone of AC-1 resistive, AC-3 squirrel cage motor, AC-4 plugging and jogging
- AC-3 squirrel cage motor
- Starts per hour
- 20 starts/h
Results
- Contactor rating required
- 17 A
- Motor full load current
- 13.99 A
- Category factor
- 1.250 x
- Recommended frame size
- 18 A
Step by step
- 1Values used
- 2Contactor sizing
- 3Contactor rating required= 17 A
- 4Motor full load current= 13.99 A
- 5Category factor= 1.250 x
- 6Recommended frame size= 18 A
Assumptions and limits
- The result is derived only from the 4 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax, fees or charges or compounding frequency into account.
- Figures are rounded for display to 3 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Frequently Asked Questions
What is the difference between AC-3 and AC-4?
AC-3 breaks running current; AC-4 breaks starting current, which is six times higher. AC-4 duty therefore demands a much larger contactor for the same motor.
Does the contactor also protect the motor?
No. A contactor only switches. Overload protection comes from a thermal overload relay or electronic protection relay in series with it.
Related Calculators
- Edge Device Compute Sizing Calculator
- Motor Sizing For Load Calculator
- Soft Starter Sizing Calculator
- Solar Powered Sensor Sizing Calculator
- VFD Sizing Calculator
- Acceleration Profile (Trapezoidal) Calculator
- ADC Sample Time Calculator
- AGV Fleet Size Calculator
- Analogue Sensor Scaling Calculator
- BLE Range Estimate Calculator
You might also need
- VFD Sizing CalculatorAlso in Robotics, Automation & Embedded
- Soft Starter Sizing CalculatorAlso in Robotics, Automation & Embedded
- Edge Device Compute Sizing CalculatorAlso in Robotics, Automation & Embedded
- Motor Sizing For Load CalculatorAlso in Robotics, Automation & Embedded
- Solar Powered Sensor Sizing CalculatorAlso in Robotics, Automation & Embedded
- Deadband Setting CalculatorAlso in Robotics, Automation & Embedded