A deadband must exceed the measurement noise, otherwise noise alone commands the actuator. It must also be wide enough that the process drift rate divided by the band gives an acceptable cycling frequency, which is what protects valves, relays and compressors from short-cycling.
Formula
Deadband
deadband >= 1.5 x peak-to-peak noise and >= 2 x drift rate / allowed actuations per hour
Worked example
With the default values below, Deadband Setting Calculator returns Recommended deadband of 1.20. Change any input above and every figure here is recalculated in your browser.
Inputs used
- Measurement noise (peak to peak)
- 0.8 units
- Sensor resolution
- 0.1 units
- Actuations tolerated per hour
- 30 actuations/h
- Process drift rate
- 2 units/h
Results
- Recommended deadband
- 1.20 units
- Expected actuations per hour
- 3.33 actuations/h
- Minimum deadband from noise
- 1.20 units
- Assessment
- Actuation rate within the target
Step by step
- 1Values used
- 2Deadband
- 3Recommended deadband= 1.20 units
- 4Expected actuations per hour= 3.33 actuations/h
- 5Minimum deadband from noise= 1.20 units
- 6Assessment= Actuation rate within the target
Assumptions and limits
- The result is derived only from the 4 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax, fees or charges or compounding frequency into account.
- Figures are rounded for display to 2 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Frequently Asked Questions
What goes wrong with too narrow a deadband?
The actuator chatters on measurement noise, wearing out contacts and valve seats and putting continuous disturbance into the process.
And too wide?
Control accuracy suffers directly: the controlled variable can sit anywhere within the band, so half the band is the minimum steady-state error.
Related Calculators
- Acceleration Profile (Trapezoidal) Calculator
- ADC Sample Time Calculator
- AGV Fleet Size Calculator
- Analogue Sensor Scaling Calculator
- BLE Range Estimate Calculator
- Cabinet Heat Load Calculator
- Camera Field Of View For Inspection Calculator
- CAN Bus Bit Timing Calculator
- Charging Dock Cycle Time Calculator
- Coin Cell Battery Life Calculator
You might also need
- Contactor Sizing CalculatorAlso in Robotics, Automation & Embedded
- Encoder Resolution CalculatorAlso in Robotics, Automation & Embedded
- Interrupt Latency CalculatorAlso in Robotics, Automation & Embedded
- Microstepping Resolution CalculatorAlso in Robotics, Automation & Embedded
- Overshoot Percentage CalculatorAlso in Robotics, Automation & Embedded
- PLC IO Count CalculatorAlso in Robotics, Automation & Embedded