Cooling Load Calculator
Work out cooling load instantly with clear inputs, formula shown and shareable results.
About Cooling Load Calculator
A room cooling load is the sum of the heat pushed in through the envelope and the heat generated inside it. This estimate applies a 25 BTU/h per square foot envelope baseline, scales it for ceiling height and solar exposure, then adds roughly 500 BTU/h of sensible plus latent gain per occupant. Dividing by 12,000 converts the load into nominal tons of refrigeration.
Formulas
Cooling load
Load = area x 25 x exposure factor x (height / 8) + occupants x 500; tons = load / 12000
- area
- Conditioned floor area (ft²)
- exposure factor
- 0.90 shaded, 1.00 average, 1.15 sunny
Supply airflow
CFM = sensible BTU/h / (1.08 x supply air ΔT)
Worked example
With the default values below, Cooling Load Calculator returns Total cooling load of 18,375. Change any input above and every figure here is recalculated in your browser.
Inputs used
- Floor areaminimum 1 ft²
- 600 ft²
- Ceiling heightminimum 6 ft
- 9 ft
- Occupantsminimum 1
- 3
- Sun exposureone of Heavily shaded, Average, Sunny / west facing
- Average
Results
- Total cooling load
- 18,375 BTU/h
- Capacity required
- 1.53 tons
- Supply airflow at 20 °F ΔT
- 851 CFM
- Load intensity
- 30.6 BTU/h/ft²
Step by step
- 1Values used
- 2Cooling load
- 3Supply airflow
- 4Total cooling load= 18,375 BTU/h
- 5Capacity required= 1.53 tons
- 6Supply airflow at 20 °F ΔT= 851 CFM
- 7Load intensity= 30.6 BTU/h/ft²
Assumptions and limits
- The result is derived only from the 4 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax, fees or charges or compounding frequency into account.
- Figures are rounded for display to 2 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
- Preliminary estimate only. A Manual J or equivalent room-by-room load calculation by a qualified HVAC engineer is required for equipment selection and code compliance.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Preliminary estimate only. A Manual J or equivalent room-by-room load calculation by a qualified HVAC engineer is required for equipment selection and code compliance.
Frequently Asked Questions
How is the Cooling Load figure worked out?
Load = area x 25 x exposure factor x (height / 8) + occupants x 500; tons = load / 12000. A room cooling load is the sum of the heat pushed in through the envelope and the heat generated inside it.
Why does ceiling height change the answer?
Load rules of thumb are calibrated to 8 ft ceilings. A taller room holds more air to cool and more wall area to gain heat through, so the load scales roughly with the height ratio.
What values do I need to enter?
This calculator takes 4 inputs: Floor area, Ceiling height, Occupants, Sun exposure. The pre-filled defaults are a realistic worked example — replace them with your own site or project figures.
Related Calculators
- Bearing Load Rating Calculator
- Cooling Time For Moulding Calculator
- Cooling Tower Capacity Calculator
- Gas Appliance Load Calculator
- Heating Load Calculator
- Air Changes Per Hour Calculator
- Air Compressor Sizing Calculator
- Air Conditioner Sizing Calculator
- Air Receiver Tank Size Calculator
- Bearing Life Calculator
You might also need
- Heating Load CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Bearing Load Rating CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Cooling Tower Capacity CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Gas Appliance Load CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Cooling Time For Moulding CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Bearing Life CalculatorAlso in HVAC, Plumbing & Mechanical Trades