Heating Load Calculator
Work out heating load instantly with clear inputs, formula shown and shareable results.
About Heating Load Calculator
Design heat loss splits into two independent paths: conduction through the building fabric, given by U x A x ΔT, and the energy needed to warm outdoor air entering by ventilation or infiltration, given by 1.08 x CFM x ΔT. Adding them yields the boiler or furnace output the building needs on the coldest design day.
Formulas
Heat loss
Q = U x A x ΔT + 1.08 x CFM x ΔT
- U
- Area-weighted U-value
- A
- Envelope area
- ΔT
- Indoor minus outdoor design temperature
Kilowatt conversion
kW = BTU/h / 3412.142
Worked example
With the default values below, Heating Load Calculator returns Total heating load of 13,752. Change any input above and every figure here is recalculated in your browser.
Inputs used
- Envelope area (walls, roof, glazing)minimum 1 ft²
- 2,200 ft²
- Average U-valueminimum 0.005 BTU/h·ft²·°F
- 0.08 BTU/h·ft²·°F
- Design temperature differenceminimum 1 °F
- 45 °F
- Ventilation / infiltration airflowminimum 1 CFM
- 120 CFM
Results
- Total heating load
- 13,752 BTU/h
- Fabric loss (U x A x ΔT)
- 7,920 BTU/h
- Ventilation loss
- 5,832 BTU/h
- Load in kilowatts
- 4.03 kW
Step by step
- 1Values used
- 2Heat loss
- 3Kilowatt conversion
- 4Total heating load= 13,752 BTU/h
- 5Fabric loss (U x A x ΔT)= 7,920 BTU/h
- 6Ventilation loss= 5,832 BTU/h
- 7Load in kilowatts= 4.03 kW
Assumptions and limits
- The result is derived only from the 4 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax, fees or charges or compounding frequency into account.
- Figures are rounded for display to 2 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
- Preliminary estimate only. Verify against a full room-by-room heat loss calculation and local energy code before sizing equipment.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Preliminary estimate only. Verify against a full room-by-room heat loss calculation and local energy code before sizing equipment.
Frequently Asked Questions
How is the Heating Load figure worked out?
Q = U x A x ΔT + 1.08 x CFM x ΔT. Design heat loss splits into two independent paths: conduction through the building fabric, given by U x A x ΔT, and the energy needed to warm outdoor air entering by ventilation or infiltration, given by 1.08 x CFM x ΔT.
Where does the 1.08 constant come from?
It is the product of air density, specific heat and 60 minutes per hour at sea level standard conditions, so 1.08 x CFM x ΔT gives sensible BTU/h directly.
What values do I need to enter?
This calculator takes 4 inputs: Envelope area (walls, roof, glazing), Average U-value, Design temperature difference, Ventilation / infiltration airflow. The pre-filled defaults are a realistic worked example — replace them with your own site or project figures.
Related Calculators
You might also need
- Cooling Load CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Bearing Load Rating CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Gas Appliance Load CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Underfloor Heating Output CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Bearing Life CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Belt Length CalculatorAlso in HVAC, Plumbing & Mechanical Trades