Cooling Water Requirement Calculator
Work out cooling water requirement instantly with clear inputs, formula shown and shareable results.
About Cooling Water Requirement Calculator
Circulating water flow is heat rejected divided by water's specific heat and the allowable temperature rise. A once-through system consumes nothing but discharges warm water; a wet tower evaporates roughly one kilogram per 2300 kilojoules rejected, and blowdown to control dissolved solids adds to make-up demand.
Formulas
Circulation rate
Flow (kg/s) = heat rejected (kW) / (4.18 x temperature rise)
Tower water balance
Evaporation = heat / 2300; blowdown = evaporation / (cycles - 1); make-up = evaporation + blowdown
Worked example
With the default values below, Cooling Water Requirement Calculator returns Circulation Rate of 29,904.3. Change any input above and every figure here is recalculated in your browser.
Inputs used
- Heat To Be Rejectedminimum 0 MW thermal
- 1,000 MW thermal
- Cooling Water Temperature Riseminimum 0 degrees C
- 8 degrees C
- Cooling Systemone of Once-through, Wet cooling tower, Air-cooled condenser
- Once-through
- Cycles Of Concentrationminimum 1.01
- 4
Results
- Circulation Rate
- 29,904.3
- Make-Up Water Required
- 0.000
- Evaporation Rate
- 0.000
- Blowdown Rate
- 0.000
Step by step
- 1Values used
- 2Circulation rate
- 3Tower water balance
- 4Circulation Rate= 29,904.3
- 5Make-Up Water Required= 0.000
- 6Evaporation Rate= 0.000
- 7Blowdown Rate= 0.000
Assumptions and limits
- The result is derived only from the 4 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax, fees or charges or compounding frequency into account.
- Figures are rounded for display to 3 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
- Cooling water abstraction and thermal discharge are subject to environmental permits, including temperature limits and impingement protection requirements.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Cooling water abstraction and thermal discharge are subject to environmental permits, including temperature limits and impingement protection requirements.
Frequently Asked Questions
Why do cooling towers consume so much water?
Cooling is achieved by evaporating water, so consumption is inherent to the mechanism. A 1000 MW thermal rejection evaporates about 430 kg/s, over 37,000 tonnes a day.
What limits cycles of concentration?
Scaling and corrosion as dissolved solids concentrate. Higher cycles save water but need better chemical treatment and may hit calcium carbonate or silica saturation limits.
Related Calculators
- Mill Power Requirement Calculator
- Solar Farm Land Requirement Calculator
- Water Cut Calculator
- Ash Content Impact Calculator
- Barrels Of Oil Equivalent Calculator
- Battery Round Trip Efficiency Calculator
- Battery Storage Sizing Calculator
- Betz Limit Power Calculator
- Biogas To Electricity Calculator
- Biomass Energy Yield Calculator
You might also need
- Water Cut CalculatorAlso in Energy, Oil, Gas & Mining
- Mill Power Requirement CalculatorAlso in Energy, Oil, Gas & Mining
- Gas Bill CalculatorAlso in Energy, Oil, Gas & Mining
- Solar Farm Land Requirement CalculatorAlso in Energy, Oil, Gas & Mining
- Biogas To Electricity CalculatorAlso in Energy, Oil, Gas & Mining
- Blending Octane CalculatorAlso in Energy, Oil, Gas & Mining