Gas Turbine Output Calculator
Work out gas turbine output instantly with clear inputs, formula shown and shareable results.
About Gas Turbine Output Calculator
Gas turbine output is quoted at ISO conditions of 15 C at sea level. Real output falls roughly 0.7% per degree above 15 C because hot air is less dense and the compressor moves less mass, and further with altitude as ambient pressure drops. Inlet filters and exhaust ducting take another 1-3%.
Formulas
Temperature derate
Factor = 1 - 0.007 x (ambient T - 15)
Altitude derate
Factor = (1 - 2.25577e-5 x altitude)^5.2559
Worked example
With the default values below, Gas Turbine Output Calculator returns Site-Rated Output of 142.811. Change any input above and every figure here is recalculated in your browser.
Inputs used
- ISO Rated Outputminimum 0 MW
- 180 MW
- Ambient Temperatureminimum -50 degrees C
- 38 degrees C
- Site Altitudeminimum 0 m
- 300 m
- Inlet And Exhaust Pressure Loss Derateaccepts 0–15 %
- 2 %
Results
- Site-Rated Output
- 142.811
- Temperature Derate Factor
- 0.83900
- Altitude Derate Factor
- 0.96494
- Output Lost Against ISO Rating
- 37.189
Step by step
- 1Values used
- 2Temperature derate
- 3Altitude derate
- 4Site-Rated Output= 142.811
- 5Temperature Derate Factor= 0.83900
- 6Altitude Derate Factor= 0.96494
- 7Output Lost Against ISO Rating= 37.189
Assumptions and limits
- The result is derived only from the 4 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax, fees or charges or compounding frequency into account.
- Figures are rounded for display to 5 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Frequently Asked Questions
Why does hot weather hurt gas turbines most?
They are constant-volume machines, so mass flow falls directly with air density. A 40 C day can cost 15-20% of ISO output — exactly when electricity demand peaks.
What can recover the lost output?
Inlet air cooling — evaporative coolers, fogging or mechanical chillers — restores much of the temperature derate and is standard in hot climates.
Related Calculators
You might also need
- Turbine Efficiency CalculatorAlso in Energy, Oil, Gas & Mining
- Fuel Cell Output CalculatorAlso in Energy, Oil, Gas & Mining
- Geothermal Heat Output CalculatorAlso in Energy, Oil, Gas & Mining
- Hydro Power Output CalculatorAlso in Energy, Oil, Gas & Mining
- Solar Farm Output CalculatorAlso in Energy, Oil, Gas & Mining
- Steam Turbine Power CalculatorAlso in Energy, Oil, Gas & Mining