Calculate generator output voltage from flux, speed and winding turns.

About Generator Voltage Calculator

Induced EMF is proportional to flux, frequency and turns. Because voltage rises with frequency at constant flux, a machine designed for 50 Hz produces 20 per cent more voltage at 60 Hz unless excitation is reduced. The volts-per-hertz relationship is why generator and transformer designs are frequency-specific and cannot simply be swapped between regions.

Formula

Generator Voltage

E = 4.44 k_f f Φ N per phase

Φ
Flux per pole in webers
N
Turns per phase
k_f
Winding distribution factor

Worked example

With the default values below, Generator Voltage Calculator returns Phase Voltage of 639.36. Change any input above and every figure here is recalculated in your browser.

Inputs used

Turns per phaseminimum 1
120
Flux per poleminimum 0 Wb
0.025 Wb
Output frequencyminimum 1 Hz
50 Hz
Winding form factoraccepts 0.5–1
0.96

Results

Phase Voltage
639.36 V
Line Voltage in Star
1,107.40 V
Volts per Turn
5.3280 V
Turns Needed for 400 V Line
44
Phase Voltage at 60 Hz
767.23 V

Step by step

  1. 1Values used
  2. 2Generator Voltage
  3. 3Phase Voltage= 639.36 V
  4. 4Line Voltage in Star= 1,107.40 V
  5. 5Volts per Turn= 5.3280 V
  6. 6Turns Needed for 400 V Line= 44
  7. 7Phase Voltage at 60 Hz= 767.23 V

Assumptions and limits

  • The result is derived only from the 4 inputs listed above. Anything not among them is not part of the calculation.
  • In particular, this calculator does not take inflation, tax or fees or charges into account.
  • Figures are rounded for display to 4 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.

How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.

Frequently Asked Questions

How is Generator Voltage calculated?

E = 4.44 k_f f Φ N per phase Induced EMF is proportional to flux, frequency and turns. Because voltage rises with frequency at constant flux, a machine designed for 50 Hz produces 20 per cent more voltage at 60 Hz unless excitation is reduced.

Why does Generator Voltage matter?

The volts-per-hertz relationship is why generator and transformer designs are frequency-specific and cannot simply be swapped between regions.