Hood Airflow Requirement Calculator
Work out hood airflow requirement instantly with clear inputs, formula shown and shareable results.
About Hood Airflow Requirement Calculator
For an enclosing hood, airflow is simply face area times the required face velocity, typically 0.5 m/s for a fume cupboard and up to 1.0 m/s for open booths. The connecting duct is then sized on transport velocity, which must be high enough to keep dust and mist entrained, usually 10 to 20 m/s.
Formulas
Hood airflow
Q = face area x face velocity
Duct size
Duct area = Q / duct velocity; diameter = sqrt(4A / pi)
Worked example
With the default values below, Hood Airflow Requirement Calculator returns Hood airflow required of 0.3600. Change any input above and every figure here is recalculated in your browser.
Inputs used
- Hood widthminimum 0.05 m
- 1.2 m
- Hood opening heightminimum 0.05 m
- 0.6 m
- Required face velocityminimum 0.05 m/s
- 0.5 m/s
- Design duct velocityminimum 1 m/s
- 10 m/s
Results
- Hood airflow required
- 0.3600 m³/s
- Airflow in cubic feet per minute
- 763 CFM
- Hood face area
- 0.720 m²
- Duct diameter required
- 214.1 mm
Step by step
- 1Values used
- 2Hood airflow
- 3Duct size
- 4Hood airflow required= 0.3600 m³/s
- 5Airflow in cubic feet per minute= 763 CFM
- 6Hood face area= 0.720 m²
- 7Duct diameter required= 214.1 mm
Assumptions and limits
- The result is derived only from the 4 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax, fees or charges or compounding frequency into account.
- Figures are rounded for display to 4 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
- Preliminary estimate only. Hood and duct design must follow a recognised industrial ventilation standard and be verified by measurement on commissioning.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Preliminary estimate only. Hood and duct design must follow a recognised industrial ventilation standard and be verified by measurement on commissioning.
Frequently Asked Questions
How is the Hood Airflow Requirement figure worked out?
Q = face area x face velocity. For an enclosing hood, airflow is simply face area times the required face velocity, typically 0.5 m/s for a fume cupboard and up to 1.0 m/s for open booths.
Why is duct velocity so much higher than face velocity?
Face velocity only has to capture contaminant at the opening. Duct velocity must keep particles suspended along the whole run, otherwise dust settles and eventually blocks the duct.
What values do I need to enter?
This calculator takes 4 inputs: Hood width, Hood opening height, Required face velocity, Design duct velocity. The pre-filled defaults are a realistic worked example — replace them with your own site or project figures.
Related Calculators
- Fire Extinguisher Rating Requirement Calculator
- First Aider Requirement Calculator
- Safety Officer Requirement Calculator
- Safety Training Hours Requirement Calculator
- Smoke Control Airflow Calculator
- Sprinkler Density Requirement Calculator
- Accident Cost Estimate Calculator
- Air Change For Contaminant Control Calculator
- Anchor Point Load Calculator
- As Low As Reasonably Practicable Cost Calculator
You might also need
- First Aider Requirement CalculatorAlso in Occupational Safety, Ergonomics & Risk
- Safety Officer Requirement CalculatorAlso in Occupational Safety, Ergonomics & Risk
- Smoke Control Airflow CalculatorAlso in Occupational Safety, Ergonomics & Risk
- Sprinkler Density Requirement CalculatorAlso in Occupational Safety, Ergonomics & Risk
- Fire Extinguisher Rating Requirement CalculatorAlso in Occupational Safety, Ergonomics & Risk
- Safety Training Hours Requirement CalculatorAlso in Occupational Safety, Ergonomics & Risk