Pump Sizing For Water Supply Calculator
Work out pump sizing for water supply instantly with clear inputs, formula shown and shareable results.
About Pump Sizing For Water Supply Calculator
Total dynamic head adds three independent requirements: the vertical lift, the friction the pipe imposes and the residual pressure needed at the outlet, converted at 2.31 feet of head per psi. Hydraulic horsepower is GPM x head / 3960, and dividing by pump efficiency gives the shaft power the motor must supply.
Formulas
Total dynamic head
TDH = static lift + friction losses + residual psi x 2.307
Power
WHP = GPM x TDH / 3960; BHP = WHP / pump efficiency
Worked example
With the default values below, Pump Sizing For Water Supply Calculator returns Total dynamic head of 101.1. Change any input above and every figure here is recalculated in your browser.
Inputs used
- Design flowminimum 0.1 GPM
- 25 GPM
- Static liftminimum 0 ft
- 40 ft
- Friction and fitting lossesminimum 0 ft
- 15 ft
- Residual pressure requiredminimum 0 psi
- 20 psi
Results
- Total dynamic head
- 101.1 ft
- Hydraulic power
- 0.638 hp
- Shaft power at 65 percent efficiency
- 0.982 hp
- Motor power
- 0.732 kW
Step by step
- 1Values used
- 2Total dynamic head
- 3Power
- 4Total dynamic head= 101.1 ft
- 5Hydraulic power= 0.638 hp
- 6Shaft power at 65 percent efficiency= 0.982 hp
- 7Motor power= 0.732 kW
Assumptions and limits
- The result is derived only from the 4 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax, fees or charges or compounding frequency into account.
- Figures are rounded for display to 3 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Frequently Asked Questions
How is the Pump Sizing For Water Supply figure worked out?
TDH = static lift + friction losses + residual psi x 2.307. Total dynamic head adds three independent requirements: the vertical lift, the friction the pipe imposes and the residual pressure needed at the outlet, converted at 2.31 feet of head per psi.
Why does the 3960 constant appear?
It folds together the weight of water and the conversion from foot-pounds per minute to horsepower, so GPM and feet of head give horsepower directly for water at standard density.
What values do I need to enter?
This calculator takes 4 inputs: Design flow, Static lift, Friction and fitting losses, Residual pressure required. The pre-filled defaults are a realistic worked example — replace them with your own site or project figures.
Related Calculators
- Water Supply Pipe Sizing Calculator
- Hot Water Cylinder Sizing Calculator
- Irrigation Pump Sizing Calculator
- Air Compressor Sizing Calculator
- Air Conditioner Sizing Calculator
- Boiler Sizing Calculator
- Booster Pump Pressure Calculator
- BTU For Room Size Calculator
- Chimney Sizing Calculator
- Condensate Drain Sizing Calculator
You might also need
- Water Supply Pipe Sizing CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Irrigation Pump Sizing CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Hot Water Cylinder Sizing CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Boiler Sizing CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Chimney Sizing CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Condenser Sizing CalculatorAlso in HVAC, Plumbing & Mechanical Trades