Booster Pump Pressure Calculator
Work out booster pump pressure instantly with clear inputs, formula shown and shareable results.
About Booster Pump Pressure Calculator
A booster only has to make up the shortfall. Required outlet pressure plus the static penalty of lifting water to the highest fixture, less the pressure already available at the inlet, gives the boost. One psi lifts water 2.31 feet, so the conversion runs both ways.
Formulas
Boost required
Boost psi = required psi + height ft / 2.307 - inlet psi
Power
WHP = GPM x boost head ft / 3960
Worked example
With the default values below, Booster Pump Pressure Calculator returns Pressure boost required of 48.01. Change any input above and every figure here is recalculated in your browser.
Inputs used
- Inlet pressure availableminimum 0 psi
- 25 psi
- Pressure required at outletminimum 0 psi
- 60 psi
- Height gain to highest outletminimum 0 ft
- 30 ft
- Design flowminimum 0.1 GPM
- 20 GPM
Results
- Pressure boost required
- 48.01 psi
- Boost expressed as head
- 110.7 ft
- Hydraulic power
- 0.559 hp
- Motor power at 60 percent efficiency
- 0.695 kW
Step by step
- 1Values used
- 2Boost required
- 3Power
- 4Pressure boost required= 48.01 psi
- 5Boost expressed as head= 110.7 ft
- 6Hydraulic power= 0.559 hp
- 7Motor power at 60 percent efficiency= 0.695 kW
Assumptions and limits
- The result is derived only from the 4 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax, fees or charges or compounding frequency into account.
- Figures are rounded for display to 3 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Frequently Asked Questions
How is the Booster Pump Pressure figure worked out?
Boost psi = required psi + height ft / 2.307 - inlet psi. A booster only has to make up the shortfall.
Should the boost be sized on peak or average flow?
On peak, because inlet pressure sags exactly when demand is highest. Sizing on average flow leaves top-floor fixtures starved at the morning peak.
What values do I need to enter?
This calculator takes 4 inputs: Inlet pressure available, Pressure required at outlet, Height gain to highest outlet, Design flow. The pre-filled defaults are a realistic worked example — replace them with your own site or project figures.
Related Calculators
- Duct Static Pressure Calculator
- Filter Pressure Drop Calculator
- Hydraulic Pump Flow Calculator
- Irrigation Pump Sizing Calculator
- Pump Sizing For Water Supply Calculator
- Submersible Pump Selection Calculator
- Air Changes Per Hour Calculator
- Air Compressor Sizing Calculator
- Air Conditioner Sizing Calculator
- Air Receiver Tank Size Calculator
You might also need
- Duct Static Pressure CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Filter Pressure Drop CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Hydraulic Pump Flow CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Irrigation Pump Sizing CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Submersible Pump Selection CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Bearing Life CalculatorAlso in HVAC, Plumbing & Mechanical Trades