UPS Backup Time Calculator
Calculate UPS runtime for a load from its installed battery capacity.
About UPS Backup Time Calculator
UPS runtime is strongly non-linear in load: halving the load more than doubles the runtime, because lower discharge current recovers capacity lost to the Peukert effect. This non-linearity is why a UPS rated for 10 minutes at full load often gives half an hour at a typical 40 per cent load.
Formula
UPS Backup Time
Runtime = usable Wh ÷ load watts, with usable capacity reduced at high discharge rates
- usable capacity
- Fraction of rated capacity available at UPS discharge rates
Worked example
With the default values below, UPS Backup Time Calculator returns Backup Runtime of 120.96. Change any input above and every figure here is recalculated in your browser.
Inputs used
- Installed battery capacityminimum 0 Ah
- 100 Ah
- Battery string voltageminimum 1 V
- 48 V
- Loadminimum 1 W
- 1,500 W
- Inverter efficiencyaccepts 0–100 %
- 90 %
- Usable capacity at high discharge rateaccepts 0–100 %
- 70 %
Results
- Backup Runtime
- 120.96 min
- Backup Runtime
- 2.0160 h
- Usable Energy
- 3,024.00 Wh
- Discharge Current
- 34.72 A
- Runtime at Half Load
- 278.21 min
Step by step
- 1Values used
- 2UPS Backup Time
- 3Backup Runtime= 120.96 min
- 4Backup Runtime= 2.0160 h
- 5Usable Energy= 3,024.00 Wh
- 6Discharge Current= 34.72 A
- 7Runtime at Half Load= 278.21 min
Assumptions and limits
- The result is derived only from the 5 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax or compounding frequency into account.
- Figures are rounded for display to 4 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Frequently Asked Questions
How is UPS Backup Time calculated?
Runtime = usable Wh ÷ load watts, with usable capacity reduced at high discharge rates UPS runtime is strongly non-linear in load: halving the load more than doubles the runtime, because lower discharge current recovers capacity lost to the Peukert effect.
Why does UPS Backup Time matter?
This non-linearity is why a UPS rated for 10 minutes at full load often gives half an hour at a typical 40 per cent load.
What values do I need to enter?
This calculator takes 5 inputs: Installed battery capacity, Battery string voltage, Load, Inverter efficiency, Usable capacity at high discharge rate. The pre-filled defaults are a realistic starting point — replace them with figures from your own environment for a result you can act on.
Related Calculators
You might also need
- Solar Panel Output CalculatorCommonly used together
- Solar Panel Size CalculatorCommonly used together
- Solar System Size CalculatorCommonly used together
- Air Conditioner Running CostAlso in Solar, Energy & Sustainability
- Annual Electricity CostAlso in Solar, Energy & Sustainability
- Battery Bank Amp Hour CalculatorAlso in Solar, Energy & Sustainability