Water Heater Recovery Rate Calculator
Work out water heater recovery rate instantly with clear inputs, formula shown and shareable results.
About Water Heater Recovery Rate Calculator
Recovery rate is the heat delivered to the water divided by the energy needed per gallon, which is 8.33 BTU per degree Fahrenheit. First hour rating adds roughly 70 percent of the stored volume to the hourly recovery, reflecting the usable hot water in the tank before incoming cold dilutes the draw.
Formulas
Recovery rate
gal/h = input BTU/h x efficiency / (8.33 x temperature rise)
First hour rating
FHR ≈ recovery gal/h + 0.7 x tank gallons
Worked example
With the default values below, Water Heater Recovery Rate Calculator returns Recovery rate of 48.0. Change any input above and every figure here is recalculated in your browser.
Inputs used
- Burner or element inputminimum 1 BTU/h
- 40,000 BTU/h
- Recovery efficiencyaccepts 20–100 %
- 80 %
- Temperature riseminimum 1 °F
- 80 °F
- Tank capacityminimum 1 gal
- 50 gal
Results
- Recovery rate
- 48.0 gal/h
- First hour rating
- 83.0 gal
- Recovery in litres
- 181.8 L/h
- Time to reheat full tank
- 62.5 min
Step by step
- 1Values used
- 2Recovery rate
- 3First hour rating
- 4Recovery rate= 48.0 gal/h
- 5First hour rating= 83.0 gal
- 6Recovery in litres= 181.8 L/h
- 7Time to reheat full tank= 62.5 min
Assumptions and limits
- The result is derived only from the 4 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax, fees or charges or compounding frequency into account.
- Figures are rounded for display to 1 decimal place, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Frequently Asked Questions
How is the Water Heater Recovery Rate figure worked out?
gal/h = input BTU/h x efficiency / (8.33 x temperature rise). Recovery rate is the heat delivered to the water divided by the energy needed per gallon, which is 8.33 BTU per degree Fahrenheit.
Why does winter performance drop?
Incoming mains water is colder, so the required temperature rise is larger and recovery in gallons per hour falls in direct proportion.
What values do I need to enter?
This calculator takes 4 inputs: Burner or element input, Recovery efficiency, Temperature rise, Tank capacity. The pre-filled defaults are a realistic worked example — replace them with your own site or project figures.
Related Calculators
- Water Heater Running Cost Calculator
- Corrosion Rate Calculator
- Feed Rate Calculator
- Gas Flow Rate Calculator
- Heat Recovery Efficiency Calculator
- Hot Water Cylinder Sizing Calculator
- Material Removal Rate Calculator
- Pump Sizing For Water Supply Calculator
- Shower Flow Rate Calculator
- Ventilation Rate Calculator
You might also need
- Water Heater Running Cost CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Corrosion Rate CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Feed Rate CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Ventilation Rate CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Gas Flow Rate CalculatorAlso in HVAC, Plumbing & Mechanical Trades
- Heat Recovery Efficiency CalculatorAlso in HVAC, Plumbing & Mechanical Trades