Diesel Generator Efficiency Calculator
Work out diesel generator efficiency instantly with clear inputs, formula shown and shareable results.
About Diesel Generator Efficiency Calculator
Generator efficiency is electrical output divided by fuel energy input. Fuel mass per hour times net calorific value gives the input in kilowatts. A well-loaded modern diesel generator reaches 38-43% at full load, falling steeply below about 50% load, which is why oversized sets are expensive to run.
Formulas
Thermal efficiency
Input (kW) = fuel (kg/h) x CV (MJ/kg) x 1000 / 3600; efficiency = output / input
Specific fuel consumption
SFC (g/kWh) = fuel (kg/h) x 1000 / output (kW)
Worked example
With the default values below, Diesel Generator Efficiency Calculator returns Thermal Efficiency of 38.603%. Change any input above and every figure here is recalculated in your browser.
Inputs used
- Electrical Outputminimum 0.01 kW
- 500 kW
- Fuel Consumptionminimum 0 L/hour
- 130 L/hour
- Fuel Densityminimum 0.01 kg/m3
- 840 kg/m3
- Net Calorific Valueminimum 0.01 MJ/kg
- 42.7 MJ/kg
Results
- Thermal Efficiency
- 38.603%
- Specific Fuel Consumption
- 218.40
- Litres Per kWh
- 0.2600
- Fuel Energy Input
- 1,295.23
Step by step
- 1Values used
- 2Thermal efficiency
- 3Specific fuel consumption
- 4Thermal Efficiency= 38.603
- 5Specific Fuel Consumption= 218.40
- 6Litres Per kWh= 0.2600
- 7Fuel Energy Input= 1,295.23
Assumptions and limits
- The result is derived only from the 4 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax, fees or charges or compounding frequency into account.
- Figures are rounded for display to 4 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Frequently Asked Questions
What SFC should a good set achieve?
195-215 g/kWh at full load for a modern medium-speed diesel. Above 240 g/kWh indicates part-load operation, poor maintenance or a fuel quality problem.
Why is part-load operation so inefficient?
Friction and auxiliary losses are nearly constant while output falls, so their share of fuel rises. Below 30% load, wet stacking and cylinder glazing also become a maintenance risk.
Related Calculators
- Battery Round Trip Efficiency Calculator
- Combined Cycle Efficiency Calculator
- Pumped Storage Efficiency Calculator
- Scrubber Efficiency Calculator
- Turbine Efficiency Calculator
- Ash Content Impact Calculator
- Barrels Of Oil Equivalent Calculator
- Battery Storage Sizing Calculator
- Betz Limit Power Calculator
- Biogas To Electricity Calculator
You might also need
- Scrubber Efficiency CalculatorAlso in Energy, Oil, Gas & Mining
- Turbine Efficiency CalculatorAlso in Energy, Oil, Gas & Mining
- Combined Cycle Efficiency CalculatorAlso in Energy, Oil, Gas & Mining
- Pumped Storage Efficiency CalculatorAlso in Energy, Oil, Gas & Mining
- Gas Bill CalculatorAlso in Energy, Oil, Gas & Mining
- Battery Round Trip Efficiency CalculatorAlso in Energy, Oil, Gas & Mining