Emergency Lighting Duration Calculator
Work out emergency lighting duration instantly with clear inputs, formula shown and shareable results.
About Emergency Lighting Duration Calculator
Emergency lighting duration is usable stored energy divided by connected load. Nameplate ampere hours are derated because deep discharge damages the battery and capacity falls with age, so eighty percent usable is a realistic planning figure. Codes require one hour where evacuation is immediate and three hours where the building may be reoccupied or sleeping risk exists.
Formula
Duration
Hours = battery Ah x voltage x usable fraction / load in watts
Worked example
With the default values below, Emergency Lighting Duration Calculator returns Duration achievable of 2.80. Change any input above and every figure here is recalculated in your browser.
Inputs used
- Battery capacityminimum 0.1 Ah
- 7 Ah
- System voltageminimum 1 V
- 12 V
- Connected emergency loadminimum 0.1 W
- 24 W
- Usable battery capacityaccepts 20–100 %
- 80 %
Results
- Duration achievable
- 2.80 h
- Duration in minutes
- 168 min
- Usable stored energy
- 67.20 Wh
- Compliance
- Meets a one hour requirement but not three hours
Step by step
- 1Values used
- 2Duration
- 3Duration achievable= 2.80 h
- 4Duration in minutes= 168 min
- 5Usable stored energy= 67.20 Wh
- 6Compliance= Meets a one hour requirement but not three hours
Assumptions and limits
- The result is derived only from the 4 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax or compounding frequency into account.
- Figures are rounded for display to 2 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
- Preliminary estimate only. Emergency lighting design, duration and testing regime must comply with the applicable standard.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Preliminary estimate only. Emergency lighting design, duration and testing regime must comply with the applicable standard.
Frequently Asked Questions
How is the Emergency Lighting Duration figure worked out?
Hours = battery Ah x voltage x usable fraction / load in watts. Emergency lighting duration is usable stored energy divided by connected load.
Why does the duty test matter more than the calculation?
Battery capacity degrades unpredictably. The annual full duration discharge test is the only reliable evidence that the system still achieves its rated duration.
What values do I need to enter?
This calculator takes 4 inputs: Battery capacity, System voltage, Connected emergency load, Usable battery capacity. The pre-filled defaults are a realistic worked example — replace them with your own site or project figures.
Related Calculators
- Lighting Level For Task Calculator
- Accident Cost Estimate Calculator
- Air Change For Contaminant Control Calculator
- Anchor Point Load Calculator
- As Low As Reasonably Practicable Cost Calculator
- Assembly Point Area Calculator
- Audit Score For Compliance Calculator
- Bow Tie Barrier Count Calculator
- Cartridge Service Life Calculator
- Chair Height Setting Calculator
You might also need
- Lighting Level For Task CalculatorAlso in Occupational Safety, Ergonomics & Risk
- Exit Capacity CalculatorAlso in Occupational Safety, Ergonomics & Risk
- Glare Index CalculatorAlso in Occupational Safety, Ergonomics & Risk
- Ladder Angle CalculatorAlso in Occupational Safety, Ergonomics & Risk
- Lifting Index CalculatorAlso in Occupational Safety, Ergonomics & Risk
- Rigging Capacity CalculatorAlso in Occupational Safety, Ergonomics & Risk