Short Circuit Current Calculator
Work out short circuit current instantly with clear inputs, formula shown and shareable results.
About Short Circuit Current Calculator
Fault current at a transformer's terminals is full load current divided by the per-unit impedance, so a 4.5% transformer gives roughly 22 times full load current. Cable impedance between the transformer and the fault reduces it, which is why the highest prospective fault current is always closest to the source.
Formula
Prospective fault current
Isc at terminals = FLC / (Z% / 100); adding cable impedance reduces it downstream
Worked example
With the default values below, Short Circuit Current Calculator returns Prospective fault current of 10.31. Change any input above and every figure here is recalculated in your browser.
Inputs used
- Transformer rating
- 500 kVA
- Secondary voltage
- 400 V
- Transformer impedance
- 4.5 %
- Cable impedance to the fault
- 8 mΩ
Results
- Prospective fault current
- 10.31 kA
- Fault current at the terminals
- 16.04 kA
- Transformer full load current
- 721.69 A
- Minimum device breaking capacity
- 16 kA
Step by step
- 1Values used
- 2Prospective fault current
- 3Prospective fault current= 10.31 kA
- 4Fault current at the terminals= 16.04 kA
- 5Transformer full load current= 721.69 A
- 6Minimum device breaking capacity= 16 kA
Assumptions and limits
- The result is derived only from the 4 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax, fees or charges or compounding frequency into account.
- Figures are rounded for display to 2 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
- Electrical results are planning estimates only. Verify against the applicable wiring rules (IEC 60364, BS 7671, NEC or local code) and have all installation work designed and checked by a qualified electrician.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Electrical results are planning estimates only. Verify against the applicable wiring rules (IEC 60364, BS 7671, NEC or local code) and have all installation work designed and checked by a qualified electrician.
Frequently Asked Questions
Why does the switchgear need to know this?
Every protective device has a breaking capacity. If the prospective fault current exceeds it, the device can fail explosively instead of clearing the fault.
Where is fault current highest?
At the transformer secondary terminals. It falls with distance as cable impedance accumulates, which is why remote sub-boards can use lower-rated devices.
Related Calculators
- Circuit Breaker Sizing Calculator
- Motor Full Load Current Calculator
- RLC Parallel Circuit Calculator
- RLC Series Circuit Calculator
- Three Phase Current Calculator
- Via Current Capacity Calculator
- Wire Size For Current Calculator
- 555 Timer Astable Calculator
- 555 Timer Monostable Calculator
- Amp Hours To Watt Hours Calculator
You might also need
- Circuit Breaker Sizing CalculatorAlso in Electrical & Electronics
- RLC Parallel Circuit CalculatorAlso in Electrical & Electronics
- RLC Series Circuit CalculatorAlso in Electrical & Electronics
- Three Phase Current CalculatorAlso in Electrical & Electronics
- Via Current Capacity CalculatorAlso in Electrical & Electronics
- Capacitance CalculatorAlso in Electrical & Electronics
