Three Phase Current Calculator
Work out three phase current instantly with clear inputs, formula shown and shareable results.
About Three Phase Current Calculator
For a balanced three-phase load, P = sqrt(3) x VL x IL x power factor, so line current is apparent power divided by sqrt(3) times line voltage. Efficiency must be applied first when the quoted power is mechanical output, since the supply must provide the losses too.
Formula
Three-phase power
P = sqrt(3) x V x I x pf; I = kVA x 1000 / (sqrt(3) x V)
Worked example
With the default values below, Three Phase Current Calculator returns Line current of 27.69. Change any input above and every figure here is recalculated in your browser.
Inputs used
- Load power
- 15 kW
- Line-to-line voltage
- 400 V
- Power factor
- 0.85
- Efficiency
- 92 %
Results
- Line current
- 27.69 A
- Apparent power
- 19.18 kVA
- Electrical input power
- 16.30 kW
- Reactive power
- 10.10 kVAr
Step by step
- 1Values used
- 2Three-phase power
- 3Line current= 27.69 A
- 4Apparent power= 19.18 kVA
- 5Electrical input power= 16.30 kW
- 6Reactive power= 10.10 kVAr
Assumptions and limits
- The result is derived only from the 4 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax or compounding frequency into account.
- Figures are rounded for display to 2 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
- Electrical results are planning estimates only. Verify against the applicable wiring rules (IEC 60364, BS 7671, NEC or local code) and have all installation work designed and checked by a qualified electrician.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Electrical results are planning estimates only. Verify against the applicable wiring rules (IEC 60364, BS 7671, NEC or local code) and have all installation work designed and checked by a qualified electrician.
Frequently Asked Questions
Where does sqrt(3) come from?
It is the ratio between line and phase quantities in a three-phase system, arising from the 120 degree phase displacement between the windings.
Why does poor power factor raise current?
Real power is fixed by the load, so a lower power factor means more apparent power and therefore more current for the same useful output — and more I squared R loss in the cables.
Related Calculators
- Line To Phase Voltage Calculator
- Motor Full Load Current Calculator
- Short Circuit Current Calculator
- Via Current Capacity Calculator
- Wire Size For Current Calculator
- 555 Timer Astable Calculator
- 555 Timer Monostable Calculator
- Amp Hours To Watt Hours Calculator
- Amplifier Gain (dB) Calculator
- Antenna Length Calculator
You might also need
- Line To Phase Voltage CalculatorAlso in Electrical & Electronics
- Short Circuit Current CalculatorAlso in Electrical & Electronics
- Via Current Capacity CalculatorAlso in Electrical & Electronics
- Capacitance CalculatorAlso in Electrical & Electronics
- Inductance CalculatorAlso in Electrical & Electronics
- VSWR CalculatorAlso in Electrical & Electronics