Line To Phase Voltage Calculator
Work out line to phase voltage instantly with clear inputs, formula shown and shareable results.
About Line To Phase Voltage Calculator
In a star-connected system the phase voltage is the line voltage divided by sqrt(3): 400 V between lines gives 230 V to neutral. Both voltages describe the same supply, which is why a three-phase distribution board offers single-phase 230 V outlets and three-phase 400 V circuits from the same cable.
Formula
Star relationships
Vphase = Vline / sqrt(3); S = sqrt(3) x Vline x Iline
Worked example
With the default values below, Line To Phase Voltage Calculator returns Phase (line-to-neutral) voltage of 230.94. Change any input above and every figure here is recalculated in your browser.
Inputs used
- Line-to-line voltage
- 400 V
- Line current
- 22 A
- Power factor
- 0.9
Results
- Phase (line-to-neutral) voltage
- 230.94 V
- Three-phase real power
- 13.72 kW
- Power per phase
- 4.57 kW
- Apparent power
- 15.24 kVA
Step by step
- 1Values used
- 2Star relationships
- 3Phase (line-to-neutral) voltage= 230.94 V
- 4Three-phase real power= 13.72 kW
- 5Power per phase= 4.57 kW
- 6Apparent power= 15.24 kVA
Assumptions and limits
- The result is derived only from the 3 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax, fees or charges or compounding frequency into account.
- Figures are rounded for display to 2 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
- Electrical results are planning estimates only. Verify against the applicable wiring rules (IEC 60364, BS 7671, NEC or local code) and have all installation work designed and checked by a qualified electrician.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Electrical results are planning estimates only. Verify against the applicable wiring rules (IEC 60364, BS 7671, NEC or local code) and have all installation work designed and checked by a qualified electrician.
Frequently Asked Questions
Is it the same in a delta connection?
No. In delta the phase voltage equals the line voltage, but the line current is sqrt(3) times the phase current.
Why 400 V and 230 V together?
They are the same system: 230 V is measured line to neutral and 400 V line to line, since 230 x sqrt(3) = 398 V.
Related Calculators
- Amp Hours To Watt Hours Calculator
- DAC Output Voltage Calculator
- Delta To Star Conversion Calculator
- Diode Forward Voltage Drop Calculator
- Electricity Unit Conversion (kW To HP) Calculator
- Resistor Value To Colour Code Calculator
- Series Battery Voltage Calculator
- Three Phase Current Calculator
- Voltage Follower Calculator
- Voltage Regulator Power Loss Calculator
You might also need
- Voltage Follower CalculatorAlso in Electrical & Electronics
- DAC Output Voltage CalculatorAlso in Electrical & Electronics
- Series Battery Voltage CalculatorAlso in Electrical & Electronics
- Three Phase Current CalculatorAlso in Electrical & Electronics
- Capacitance CalculatorAlso in Electrical & Electronics
- Inductance CalculatorAlso in Electrical & Electronics