Relay Contact Life Calculator
Work out relay contact life instantly with clear inputs, formula shown and shareable results.
About Relay Contact Life Calculator
Contact life falls steeply with load current — roughly as the inverse 1.5 power — and depends heavily on load type. Inductive loads cut life to around a third of resistive because the arc on break is far more energetic, and lamp inrush is worse still.
Formula
Contact life
life = rated operations x (rated current / load current)^1.5 x load type factor
Worked example
With the default values below, Relay Contact Life Calculator returns Expected operations of 75,308. Change any input above and every figure here is recalculated in your browser.
Inputs used
- Rated electrical life
- 100,000 operations
- Load current
- 6 A
- Rated contact current
- 10 A
- Load typeone of Resistive, Inductive (AC-15 / DC-13), Lamp / capacitive inrush, Motor
- Inductive (AC-15 / DC-13)
Results
- Expected operations
- 75,308 operations
- Combined derating factor
- 0.7531 x
- Years at one operation per hour
- 8.60 years
- Load type factor
- 0.350 x
Step by step
- 1Values used
- 2Contact life
- 3Expected operations= 75,308 operations
- 4Combined derating factor= 0.7531 x
- 5Years at one operation per hour= 8.60 years
- 6Load type factor= 0.350 x
Assumptions and limits
- The result is derived only from the 4 inputs listed above. Anything not among them is not part of the calculation.
- In particular, this calculator does not take inflation, tax or compounding frequency into account.
- Figures are rounded for display to 4 decimal places, so totals built from several rounded parts can differ slightly from the unrounded arithmetic.
How these calculators are built and tested is described on the Methodology page. If a figure looks wrong, please report it.
Frequently Asked Questions
Why do inductive loads destroy contacts?
Interrupting current in an inductance produces an arc that transfers metal from one contact to the other. Freewheel diodes on DC and RC snubbers on AC greatly extend life.
Should I use a contactor or a solid-state relay?
For frequent switching of inductive loads, a solid-state relay has no contacts to erode. The trade is on-state voltage drop, heat and no galvanic isolation of the load.
Related Calculators
- Coin Cell Battery Life Calculator
- Sleep Mode Battery Life Calculator
- Acceleration Profile (Trapezoidal) Calculator
- ADC Sample Time Calculator
- AGV Fleet Size Calculator
- Analogue Sensor Scaling Calculator
- BLE Range Estimate Calculator
- Cabinet Heat Load Calculator
- Camera Field Of View For Inspection Calculator
- CAN Bus Bit Timing Calculator
You might also need
- Coin Cell Battery Life CalculatorAlso in Robotics, Automation & Embedded
- Sleep Mode Battery Life CalculatorAlso in Robotics, Automation & Embedded
- Contactor Sizing CalculatorAlso in Robotics, Automation & Embedded
- Deadband Setting CalculatorAlso in Robotics, Automation & Embedded
- Encoder Resolution CalculatorAlso in Robotics, Automation & Embedded
- Interrupt Latency CalculatorAlso in Robotics, Automation & Embedded